This paper presents the application of a controlled switching system for energizing a 500/230/33 kV auto transformer with delta connected tertiary winding in Colcabamba substation, Peru. Controlled switching is used to reduce grid voltage drop during no load energization of power transformer due to high inrush current during its charging; specifically, controlled deenergization to lock residual flux at lowest possible level followed by controlled energization considering residual flux to achieve inrush current mitigation. A verified simple and easily applicable approach to estimate residual flux in individual phases based on inrush peaks obtained during first time energization of power transformers is used to further reduce inrush current to best possible levels.
机译:本文介绍了可控开关系统在秘鲁科尔卡班巴变电站为500/230/33 kV三角连接的三次绕组自动变压器供电的应用。可控开关用于减少电力变压器在充电过程中由于浪涌电流高而在空载时产生的电网电压降;具体而言,可控制的去激励将残余磁通锁定在最低可能的水平,然后再进行可控制的通电,考虑残余磁通以减轻浪涌电流。一种经过验证的简单易用的方法可用于根据电力变压器首次通电期间获得的涌入峰值来估算各个相中的剩余磁通,以将涌入电流进一步降低至最佳水平。