METHOD OF CRITICAL DISTANCES FOR STOCHASTIC ASSESSMENT OF VOLTAGE SAGS IN A MESHED DISTRIBUTION SYSTEM

机译:网格配电系统中电压暂降的随机评估临界距离方法

获取原文
获取原文并翻译 | 示例

摘要

This paper is concerned with the method of critical distances for stochastic assessment of voltage sags in a large complicated distribution system. As the system is meshed, the method of critical distances is extended. Critical percentage of the feeders is developed from the critical distance in convenience to use the data provided by the industrial customer. The three phase short circuit faults in different locations, i.e. in the distribution system and in the public transmission system, are investigated detailed. The critical percentage of the feeders for each PCC is calculated. The results show that short circuit faults in the distribution system at 110kV level will cause serious voltage sags, the spurious equipment trips are mainly due to the faults in the onsite system, not in the public utility system.
机译:本文涉及用于大型复杂配电系统中的电压暂降随机评估的临界距离方法。随着系统的网格化,临界距离的方法得到了扩展。关键进料器的百分比是从关键距离发展而来的,以方便使用工业客户提供的数据。详细研究了不同位置,即配电系统和公共输电系统中的三相短路故障。计算每个PCC的进料器的临界百分比。结果表明,110kV级别的配电系统中的短路故障将导致严重的电压骤降,虚假设备跳闸主要是由于现场系统而非公共事业系统中的故障引起的。