首页> 外文会议>International symposium on high voltage engineering;ISH2003 >Detecting degree of water treeing in XLPE power cable systemsusing polarisation and depolarisation current method
【24h】

Detecting degree of water treeing in XLPE power cable systemsusing polarisation and depolarisation current method

机译:使用极化和去极化电流法检测XLPE电力电缆系统中水树的程度

获取原文

摘要

Insulation degradation is a major concernfor aged power cable systems. Water tree is the maincause of insulation degradation of polymer insulatedcable and is the main cause of its failure in longservice. In addition to the magnitude and voltagedependence of the dielectric response (also calleddegree of non-linearity) used to evaluate the conditionof the insulation, another method of assessing thecondition of XLPE power cable is presented in thispaper. The proposed method utilises the dischargecharacteristics of the cable. In order to convert thevalue of the proposed method into figure of merit thatgives a figure for the insulation condition, tan valuesare calculated using Fourier transformation. Amongseveral other methods for interpretation, the proposedmethod is shown to be temperature independent thatcan be used for on-site diagnosis of cable. However itsapplicability to cable diagnosis requires furtherjustification through additional research work.
机译:绝缘退化是老化的电力电缆系统的主要问题。水树是聚合物绝缘电缆绝缘性能下降的主要原因,也是其长期使用失败的主要原因。除了用于评估绝缘状况的介电响应(也称为非线性度)的大小和电压依赖性之外,本文还提出了另一种评估XLPE电力电缆状况的方法。所提出的方法利用了电缆的放电特性。为了将所提出的方法的值转换为给出绝缘条件图的品质因数,使用傅立叶变换来计算tan值。在许多其他解释方法中,所提出的方法显示出与温度无关,可用于电缆的现场诊断。然而,其在电缆诊断中的适用性需要通过额外的研究工作进一步证明。