首页> 外文期刊>昭和電線レビュ- >Study on diagnostic method for water treed XLPE cables by distorted AC loss current
【24h】

Study on diagnostic method for water treed XLPE cables by distorted AC loss current

机译:交流损耗电流失真对水树交联聚乙烯电缆诊断方法的研究

获取原文
获取原文并翻译 | 示例

摘要

It has been reported in polymer insulation that the ac loss current in phase to applied voltage is distorted with developing of water trees. We have obtained the distorted ac loss current from the water treed XLPE sheets. The observed wave forms were compared with the calculated ones by the model which takes account of a non-linear dependence of conduction current through the water treed region. It has been found that this model can explain qualitatively the changes of the relative magnitude of 3rd harmonic wave to the fundamental one and the phase of 3rd harmonic wave of ac loss current.
机译:据报道,在聚合物绝缘中,随着水树的发展,与施加电压同相的交流损耗电流会失真。我们从水树状XLPE板中获得了失真的交流损耗电流。模型将观测到的波形与计算波形进行了比较,该模型考虑了通过水树区域的导电电流的非线性依赖性。已经发现,该模型可以定性地解释交流损耗电流的三次谐波相对于基波的相对幅值和三次谐波的相位的变化。