Aiming at the problems of SF6 electric equipment latent period of internal overheating failure and difficult monitoring, and the SF6 gas in the GIS isolation switch gas chamber has the characteristics of non-isothermal flow with invariable volume. The coupled fluid-thermal field is established of SF6 based on the heat conduction differential equation, the fluid motion control equation and the radiation heat transfer equation. The COMSOL finite element simulation software was used to calculate the different temperature of fault points (333.15K~453.15K). The distribution of temperature, velocity and pressure of SF6 gas in different positions of an isolated switch gas chamber is calculated, according to the simulation results, it is the first time to demonstrate the effectiveness of using pressure to detect the internal overheating failure in the gas chamber.
机译:针对SF6电器设备内部过热故障潜伏期长,监控困难的问题,GIS隔离开关气室内的SF6气体具有非等温流量不变的特点。基于导热微分方程,流体运动控制方程和辐射传热方程,建立了SF6流体-热耦合场。使用COMSOL有限元模拟软件计算故障点的不同温度(333.15K〜453.15K)。计算了隔离开关气室不同位置的SF6气体的温度,速度和压力的分布,根据仿真结果,这是首次证明利用压力检测气体内部过热故障的有效性。室。