Effects of Longitudinal Fault on Pilot Zero-Sequence Directional Component in Four Parallel Transmission Lines Under Different Voltage Levels

机译:纵向故障对不同电压水平下四条并联输电线路先导零序方向分量的影响

获取原文

摘要

When asymmetric longitudinal fault occurs in parallel transmission lines, the shift of load current and mutual inductance may produce large zero-sequence current in the healthy line, leading to the improper operation of pilot zero-sequence directional component with voltage compensation. This paper takes four parallel transmission lines under different voltage levels as research object, analyzing the zero-sequence fault characteristics and pilot zero-sequence directional protection performance in longitudinal fault, considering the influence of the potential transformer position, the electrical connection between different lines, the zero-sequence impedance of systems, and the partial coupling effect. Then the improper operation mechanism of pilot zero-sequence directional protection in the healthy line, which has a strong or weak electrical connection with the faulty line, is presented respectively. Moreover, potential solutions based on negative-sequence components, transmission power and smart substation are proposed.
机译:当并联输电线路中出现不对称纵向故障时,负载电流和互感的偏移可能会在健康线路中产生较大的零序电流,从而导致带电压补偿的先导零序方向性组件操作不当。本文以四条不同电压等级的平行输电线路为研究对象,分析了纵向故障中的零序故障特性和零序先导方向保护性能,并考虑了电压互感器位置,不同线路之间电气连接的影响,系统的零序阻抗以及部分耦合效应。然后分别提出了健康线路零故障方向保护的误动作机理,该故障线路与故障线路有强电连接或弱电连接。此外,提出了基于负序分量,传输功率和智能变电站的潜在解决方案。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号