首页> 外文期刊>Generation, Transmission & Distribution, IET >Novel pilot protection principle for high-voltage direct current transmission lines based on fault component current characteristics
【24h】

Novel pilot protection principle for high-voltage direct current transmission lines based on fault component current characteristics

机译:基于故障分量电流特性的高压直流输电线路新型先导保护原理

获取原文
获取原文并翻译 | 示例
           

摘要

For high-voltage direct current (HVDC) transmission systems, the transient fault current characteristics are that: if the fault point is over the line, the fault component current measured at both converter stations would be increased and they have the same changing direction. If the fault point is beyond the line, the fault component current measured at one converter station is increasing and the fault component current measured at the other converter station is decreasing, so they have the opposite changing direction. According to this characteristic, a novel pilot protection principle for HVDC transmission line based on fault component current is proposed here. The principle proposed has no limitation to the sampling frequency. A fault, whether it occurs in the line or beyond the line, can be effectively identified only using the fault component current at both converter stations. At the same time, the setting criterion of the fault component current is also given. The simulation results show that the new method can identify the faults reliably and rapidly. The study is promising to have significant theoretical and practical value.
机译:对于高压直流(HVDC)传输系统,瞬态故障电流特性是:如果故障点在线路上,则两个换流站处测得的故障分量电流将增加,并且它们具有相同的变化方向。如果故障点在线路之外,则在一个换流站处测得的故障分量电流将增加,而在另一换流站处测得的故障分量电流将减小,因此它们的变化方向相反。根据这一特性,提出了一种基于故障分量电流的高压直流输电线路先导保护原理。提出的原理对采样频率没有限制。仅在两个换流站上都使用故障分量电流,才能有效地识别出故障,无论是发生在线路内还是线路外。同时给出了故障分量电流的设定准则。仿真结果表明,该方法能够可靠,快速地识别出故障。该研究有望具有重要的理论和实践价值。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号