The live line inspection device of poor insulators on DC transmission line was developed, and the distributed voltage along insulators on ±500 kV DC transmission line was inspected. The results show that the potential distribution of insulator string on DC transmission line is the same with that on AC transmission line, which is with U distribution, and affected more with the performances of single insulator. The inspection device can meet the requirements of live working inspection under ±500 kV DC transmission line. The research has the important meaning for reducing the outage duration of ±500 kV DC transmission line and improving safe and stable operation of power grid.
机译:开发了直流输电线路绝缘子不良的带电检查装置,并对±500 kV直流输电线路绝缘子的分布电压进行了检查。结果表明,直流输电线路上绝缘子串的电位分布与交流输电线路上的绝缘子串的电位分布相同,呈U分布,并且受单个绝缘子性能的影响更大。该检查装置可以满足±500kV直流输电线路带电作业检查的要求。该研究对于缩短±500 kV直流输电线路的停电时间,提高电网安全稳定运行具有重要意义。