摘要

The possibility of limiting the amplitude of the turbine shaft line torsional vibrations by introducing additional units into the automatic excitation regulator of the generator is studied. The mathematical model of the power system, including the electric and mechanical subsystem of the turbine, is developed. The structure of an automatic excitation regulator is given. A quadratic controller is implemented that makes to reduce the amplitudes of torsional oscillations. The system is modeled without the controller and with it. The dependence of the amplitude of the torsional oscillations on the gain factor of the controller is obtained. By this dependence it can be concluded that the increase of the coefficient of the quadratic controller makes it possible to reduce the amplitude of the oscillations.
机译:研究了通过将附加单元引入发电机的自动励磁调节器来限制涡轮机轴线扭转振动的幅度的可能性。开发了动力系统的数学模型,包括涡轮机的电气和机械子系统。给出了自动励磁调节器的结构。实施二次控制器,以减小扭转振动的幅度。该系统的建模没有控制器,也没有控制器。获得了扭转振动的幅度对控制器增益因子的依赖性。通过这种依赖性可以得出结论,二次控制器的系数的增加使得可以减小振荡的幅度。