Temperature Measurement on Operating Recessed Lighting Fixtures

机译:操作嵌入式照明灯具的温度测量

获取原文

摘要

Potentially hazardous temperatures may result from adding thermal insulation in the attic above recessed incandescent lighting fixtures. The National Electric Code for 1978 specifies that '...thermal insulation shall not be installed within three inches of a recessed fixture enclosure, wiring compartment or ballast and shall not be so installed above the fixture as to entrap heat and prevent the free circulation of air...' The purpose of this investigation was to determine the effectiveness of various protective barriers in maintaining the requisite three-inch spacing and in preventing over-temperature conditions when loose-fill insulation is installed around recessed lighting fixtures. For the devices tested, the results indicate that properly installed open-top barriers are sufficient to allow the fixture and associated branch circuit wiring to operate within specified ratings. However, a barrier closed at the top by any method, can cause branch circuit wiring, the external surface of the barrier and/or parts of the fixture to operate at temperatures above those designated as 'safe'.