首页> 外文期刊>Computers and Electrical Engineering >Effects of the curve type of overcurrent functions and the location of analyzed faults on the optimal coordination of directional overcurrent protections
【24h】

Effects of the curve type of overcurrent functions and the location of analyzed faults on the optimal coordination of directional overcurrent protections

机译:曲线型过流函数的影响及分析故障的位置对方向性过电流保护的最优协调

获取原文
获取原文并翻译 | 示例
           

摘要

The time-current curve type and the considered fault locations influence the optimal coordination of directional overcurrent protections. It is shown that curve type can determine the feasibility of having solutions and the feasibility of obtaining reasonably low trip times. It is also shown that constraints for faults near to the main relay location must be complemented with those of other fault locations. In general, the use of Extremely Inverse curves implies a faster protection in the analyzed cases. This is because this coordination depends on the ratio between the currents seen by each relay, and Extremely Inverse curves have the greatest inclination in time-current graphs. The backup action for faults near to the remote line end of main relays can be very slow with Extremely Inverse curves in some cases; therefore, an analysis of benefits and drawbacks of using each curve type should be performed in each analyzed case.
机译:None

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号