首页> 外文会议>電気学会研究会資料 電力技術研究会 >A Study on Optimal Protection Coordination of Directional Overcurrent Relay considering Fault Ride Through Capability using Genetic Algorithm
【24h】

A Study on Optimal Protection Coordination of Directional Overcurrent Relay considering Fault Ride Through Capability using Genetic Algorithm

机译:基于遗传算法的故障穿越能力的方向性过电流继电器最优保护配合研究

获取原文
获取原文并翻译 | 示例

摘要

Fault Ride Through (FRT) capability of Distributed Generation (DG) contributes distribution system stability during disturbance. Clearing fault by Directional OverCurrent Relay (DOCR) before disconnection of DG is important to maintain system stability. In this paper, we optimize a pickup current and Time Dial Setting (TDS) of DOCR using proposed objective function (OF). This proposed OF includes a term which decreases chance to disconnect DG during fault. The proposed OF is compared with conventional OF which minimize only overall relays operating times on modified IEEE 30 bus test system with inverter based DGs. Results show that relay setting values, obtained by proposed OF using MATLAB, prevent to disconnect the DG during fault with higher probability.
机译:分布式发电(DG)的故障穿越(FRT)能力有助于扰动期间配电系统的稳定性。在断开DG之前通过定向过流继电器(DOCR)清除故障对于保持系统稳定性很重要。在本文中,我们使用提出的目标函数(OF)优化了DOCR的启动电流和时间拨号设置(TDS)。该提议的OF包括减少故障期间断开DG的机会的术语。所提议的OF与传统OF相比,后者在带有逆变器的DG的改进的IEEE 30总线测试系统上仅使整个继电器的运行时间最小化。结果表明,通过使用MATLAB提出的OF所获得的继电器设定值可以防止发生故障时DG断开的可能性更高。