首页> 外文期刊>Applied thermal engineering: Design, processes, equipment, economics >Analysis of a district heating system using waste heat in a distributed cooling data center
【24h】

Analysis of a district heating system using waste heat in a distributed cooling data center

机译:分布式冷却数据中心中使用废热的地区供热系统分析

获取原文
获取原文并翻译 | 示例
           

摘要

With the rapid development of the data center industry, a major source of waste energy is created through the increasing demand for cloud-based connectivity and performance. A recent study demonstrated that data centers are responsible for approximately 1.3% of total global electricity usage. In addition, nearly 40% of this power is consumed by computer room air conditioning (CRAC) systems for cooling the servers, which creates a significant stream of waste heat. The waste heat in a data center has a low quality; therefore, recovery and reuse of the waste eat is a challenge. In this study, a district heating system solution using waste heat in a data center was introduced. A distributed cooling solution was discussed to improve the quality of this waste heat. Then, heat pump technology was used to further raise the quality. The energy-saving effect was theoretically compared with coal-fired heating. A new index PUEwh was defined to evaluate the power utilization effectiveness of the data center with the heat recovery system. This waste heat district heating solution was implemented at a data center in Hohhot, China, and measurements demonstrated that the PUEwh of this data center was 0.13.
机译:随着数据中心行业的快速发展,通过对基于云的连通性和性能的需求的增加来创造了一种主要的废能来源。最近的一项研究表明,数据中心负责全球全球电力使用的1.3%。此外,电脑室空调(CRAC)系统消耗了近40%的电力,用于冷却服务器,这产生了大量的废热流。数据中心的废热具有低质量;因此,废物吃的恢复和重用是一项挑战。在这项研究中,引入了在数据中心中使用废热的区域加热系统解决方案。讨论了分布式冷却溶液以提高这种废热的质量。然后,使用热泵技术进一步提高质量。与燃煤加热理论上的节能效果理论上是。定义了一个新的索引普韦瓦特,以评估数据中心与热回收系统的电力利用效果。这种废热区供热解决方案在呼和浩特,中国的数据中心实施,测量表明该数据中心的普烟为0.13。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号