首页> 外文期刊>International Journal of Photoenergy >Line-End Voltage and Voltage Profile along Power Distribution Line with Large-Power Photovoltaic Generation System
【24h】

Line-End Voltage and Voltage Profile along Power Distribution Line with Large-Power Photovoltaic Generation System

机译:具有大功率光伏发电系统的线路端电压和电压曲线

获取原文
获取原文并翻译 | 示例
       

摘要

In recent years, the introduction of the photovoltaic generation system (PV system) has been increasing by promoting the use of renewable energy. It has been feared that the reverse current from the PV system may cause an unacceptable level of voltage rise at the interconnection node in the power distribution system. This paper discusses the effects of the reverse current on the voltage rise and fall characteristics of the interconnection node and the voltage profiles along the power distribution line. When the line current on the circuit is small, the voltage on the line monotonically increases from the sending end to the receiving end. When a relatively large current flows, it causes a voltage reduction near the distribution substation. Furthermore, on the basis of the voltage aspects in the power distribution system with a large PV system, the allowable limits of the line current and the output power from PV system are investigated.
机译:近年来,通过促进可再生能源的使用,光伏发电系统(PV系统)的引入一直在增加。 已经担心PV系统的反向电流可能导致配电系统中的互连节点处的不可接受的电压升高。 本文讨论了反向电流对互连节点的电压上升和落下特性的影响和沿功率分配线的电压谱。 当电路上的线电流小时,线路上的电压从发送端单调增加到接收端。 当电流相对大的流动时,它会导致分配变电站附近的电压降低。 此外,根据具有大PV系统的配电系统中的电压方面,研究了线电流的允许极限和来自PV系统的输出功率。