首页> 外文期刊>Journal of Failure Analysis and Prevention >Creep Failure and Prevention in Aluminum Wound Distribution Transformers
【24h】

Creep Failure and Prevention in Aluminum Wound Distribution Transformers

机译:铝绕配电变压器的蠕变故障及预防

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an experimental study on electrical properties and creep behavior of thermo-mechanically processed 6060 aluminum alloy wire to assess its suitability as a winding conductor in place of electric conductor grade aluminum wire in distribution transformers. Electrical resistivity and the stress exponent and activation energy for creep were measured for both thermo-mechanically processed 6060 aluminum alloy and electric conductor grade aluminum wire. An algorithm is given for estimate the life and switching capability of the distribution transformers considering creep. The results of this study can be used as a guide to select the creep resistant winding material for designing and producing reliable distribution transformers and is valuable especially in power deficient areas, poorly designed and haphazardly expanded power distribution networks where repeatedly energized aluminum wound distribution transformers may fail due to creep in the high voltage winding conductors.
机译:本文对热机械加工的6060铝合金线的电性能和蠕变行为进行了实验研究,以评估其代替配电变压器中的电导体级铝线作为绕组导体的适用性。测量了热机械加工的6060铝合金和电导体级铝线的电阻率,应力指数和蠕变活化能。给出了一种考虑蠕变的估计配电变压器寿命和开关能力的算法。这项研究的结果可作为选择抗蠕变绕组材料以指导设计和生产可靠的配电变压器的指南,特别是在电力不足,设计欠佳且随意扩展的配电网络(可能反复通电的铝绕制配电变压器)中具有重要意义。由于高压绕组导体的蠕变而导致故障。