Aims: To evaluate hydrogen peroxide vapour (H2O2) for its ability to inactivate Bacillus spores within a laboratory-scale heating, ventilation and air-conditioning (HVAC) duct system. Methods and Results: Experiments were conducted in a closed-loop duct system, constructed of either internally lined or unlined galvanized metal. Bacterial spores were aerosol-deposited onto 18-mm-diameter test material coupons and strategically placed at several locations within the duct environment. Various concentrations of H2O2 and exposure times were evaluated to determine the sporicidal efficacy and minimum exposure needed for decontamination. For the unlined duct, high variability was observed in the recovery of spores between sample locations, likely due to complex, unpredictable flow patterns within the ducts. In comparison, the lined duct exhibited a significant desorption of the H2O2 following the fumigant dwell period and thus resulted in complete decontamination at all sampling locations. Conclusions: These findings suggest that decontamination of Bacillus spore-contaminated unlined HVAC ducts by hydrogen peroxide fumigation may require more stringent conditions (higher concentrations, longer dwell duration) than internally insulated ductwork. Significance and Impact of the Study: These data may help emergency responders when developing remediation plans during building decontamination.
机译:目的:评估过氧化氢蒸气(H 2 O 2 )在实验室规模的加热,通风和空调(HVAC)管道内灭活芽孢杆菌孢子的能力。系统。方法和结果:实验是在由内部衬里或未衬里的镀锌金属构成的闭环管道系统中进行的。将细菌孢子气溶胶沉积在直径为18 mm的测试材料试样上,并策略性地放置在管道环境中的多个位置。评估了各种浓度的H 2 O 2 和暴露时间,以确定杀菌效果和杀菌所需的最低暴露量。对于无衬里的管道,在样品位置之间的孢子回收率中观察到高变异性,这可能是由于管道内复杂,不可预测的流动模式所致。相比之下,衬里导管在熏蒸剂停留期后表现出H 2 O 2 的显着解吸,因此导致在所有采样位置都完全被净化。结论:这些发现表明,与内部绝缘的管道系统相比,通过过氧化氢熏蒸对芽孢杆菌污染的无衬套HVAC管道进行消毒可能需要更严格的条件(更高的浓度,更长的停留时间)。研究的意义和影响:这些数据可能有助于在建筑物净化过程中制定补救计划时的应急人员。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号