Associate editor Chris Ermides replies: No and yes. The section from the International Residential Code to which you're referring (R502.2.2) says that decks have to be designed for both vertical and lateral loads. That part has been on the books for years and is meant to keep the deck from pulling away from the house. But the 2009 IRC does have a new provision that gets specific about what's required to support a lateral load.rnThe new code section (R502.2.2.3) states that "hold-down tension devices" be installed in at least two locations per deck. Whether you are attaching a deck that's 3 ft. long or 30 ft. long, you will be required to use the hold-down tension devices in two locations.
机译:副编辑克里斯·埃尔米德斯(Chris Ermides)答复:否,是的。您要参考的《国际住宅规范》(R502.2.2)中的部分指出,甲板必须设计为既能承受垂直载荷又能承受水平载荷。该部分已在书本上使用多年,目的是防止甲板从房子上拉开。但是2009 IRC确实有一条新规定,具体规定了承受侧向载荷的要求。rn新法规部分(R502.2.2.3)规定,“压紧张力装置”应安装在每个甲板至少两个位置。无论您要安装3英尺长或30英尺长的甲板,都将需要在两个位置使用压紧张力装置。