Shaking table tests were carried out on five 1100-kV ultra-high voltage (UHV) porcelain transformer bushings to evaluate their seismic performance. Finite-element models of the bushings were established. The influence of different types of connection on the seismic responses of the oil-side bushings was analysed. A simplified method to rapidly estimate the seismic responses of transformer bushings was implemented. Test results indicated that the safety factors of the porcelain insulators met the seismic requirements of the relevant standards. However, the metal flange might have cracked in earthquakes. Increasing the rotational stiffness of the connection reduced the seismic responses of the oil-side bushings. The mode mass participating coefficients of the first mode of the UHV transformer bushings were between 0.6 and 0.65. The simplified method presented in this paper was able to estimate the seismic responses of the 1100-kV UHV transformer bushings, with results close to those of the shaking table tests.
机译:在五个1100 kV超高压(UHV)瓷制变压器套管上进行了振动台测试,以评估其抗震性能。建立了套管的有限元模型。分析了不同连接方式对油侧衬套地震响应的影响。一种简化的方法可以快速估算变压器套管的地震响应。测试结果表明,瓷绝缘子的安全系数符合有关标准的抗震要求。但是,金属法兰可能在地震中破裂。连接的旋转刚度增加,会降低油侧衬套的地震响应。 UHV变压器套管第一模式的模式质量参与系数在0.6到0.65之间。本文提出的简化方法能够估算1100 kV特高压变压器套管的地震响应,其结果接近于振动台试验。