摘要

The merit of a proposed non-destructive method of assessing the breakdown voltage of stator-coil insulation by means of high-voltage direct current is examined. The proposal is to measure the steady-state leakage current at successive increments of applied voltage and predict a breakdown value from the trend of the plotted results. Laboratory tests applied to a range of specimens of sheet insulation, including a number with artificially-formed faults, indicate that the only breakdown which can be predicted by this method is that across air paths external to the specimen. Tests carried out on a complete high-voltage stator winding and on single stator coils give similar results. No assessment of slot-insulation quality is possible: the only increase in current, suggestive of approaching failure, results from end-winding leakage and discharge effects. Surface contamination of the end-winding and even quite extraneous discharges, when present, have a marked influence on the current measurements. It is concluded that the high-voltage d.c. method of testing investigated has no valid basis for non-destructively indicating the service-ability of the insulation of high-voltage machines.
机译:研究了一种通过高压直流电评估定子线圈绝缘击穿电压的无损方法的优点。建议是在施加的电压连续增加时测量稳态泄漏电流,并根据绘制结果的趋势预测击穿值。对一系列薄板绝缘样品进行的实验室测试,包括许多具有人为形成的断层的样品,表明通过这种方法可以预测的唯一击穿是样品外部的空气路径。在完整的高压定子绕组和单个定子线圈上进行的测试得出相似的结果。无法评估插槽绝缘质量:只有电流增加,暗示接近故障,这是由端部绕组泄漏和放电效应引起的。端部绕组的表面污染,甚至存在非常多余的放电(如果存在),都会对电流测量产生显着影响。结论是高压直流电。所研究的测试方法没有无损表明高压机器绝缘的使用寿命的有效依据。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号