Root Cause Analysis of AC Overcurrent in July 2020 San Fernando Disturbance

机译:7月20日SAN Fernando扰动中AC过流的根本原因分析

获取原文
获取原文并翻译 | 示例

摘要

On July 7 2020, approximately 1000 MW reduction in solar photovoltaic (PV) output was experienced by the bulk power system in Southern California after a three-phase fault. Disturbance analysis indicates that instantaneous AC current caused inverter tripping. The projection of the root cause of AC overcurrent from the NERC report is that inverter current control is not tight. This letter provides a quantitative analysis on ac overcurrent and addresses the following questions: (i) what type of current controls may lead to ac overcurrent and (ii) how controller parameters and grid strength may influence ac overcurrent. The letter provides frequency-domain analysis and time-domain simulation results of a grid-integrated inverter to illustrate the effect of control parameters and grid strength on ac overcurrent.