An adaptive scheme is proposed for determining the amount of load to be shed by underfrequency relays based on the observed initial slope of the frequency deviation. following the system separation. This initial slope contains all the information required to estimate that size of the step change in load caused by the system separation and to forecast the depth and even the approximate time of the maximum frequency dip. From this observation, the first step of load shedding can be set up adaptively, with additional steps to follow at prescribed intervals and amounts. The first step is considered the most important and is selected arbitrarily at one-half the static load shed target, with additional increments of about 0.1 per unit to be shed at 0.3 Hz increments until the dynamic load shed amount has been reached.
机译:提出了一种自适应方案,用于基于观察到的频率偏差的初始斜率来确定低频继电器要减轻的负载量。按照系统分离。该初始斜率包含所有必要信息,以估计由系统分离引起的负载阶跃变化的大小,并预测深度甚至最大频率骤降的近似时间。从这个观察结果来看,可以自适应地设置减载的第一步,并按照规定的间隔和数量执行其他步骤。第一步被认为是最重要的,它是在静态负荷降低目标的一半时任意选择的,并以0.3 Hz的增量以每单位约0.1的额外增量降低,直到达到动态负荷降低量为止。