首页> 外文期刊>IEEE Transactions on Power Systems >Analysis on the control principle of the active DC filter in theLindome converter station of the Konti-Skan HVDC link
【24h】

Analysis on the control principle of the active DC filter in theLindome converter station of the Konti-Skan HVDC link

机译:Konti-Skan HVDC链路的Lindome换流站中有源直流滤波器的控制原理分析

获取原文
获取原文并翻译 | 示例
           

摘要

The control principle of a hybrid passive-active DC filterninstalled in the Lindome HVDC converter station is analyzed in thisnpaper. The controller of the active filter includes two basic functions:nan integrator and a compensator. The main advantage of the Lindomencontroller is its simple structure for implementation in a digitalnsignal processor (DSP). The drawbacks of this controller are its longnresponse time, low stability margin and the filtering of an unnecessarynnumber of frequencies. An alternative control strategy using a number ofnnotch filters has been investigated. The notch filters can be tuned tonthose frequencies that need to be damped. This controller gives a muchnshorter system response time and improved stability margin
机译:本文分析了安装在Lindome HVDC换流站中的混合型无源-有源DC滤波器的控制原理。有源滤波器的控制器包括两个基本功能:积分器和补偿器。 Lindomencontroller的主要优点是其在数字信号处理器(DSP)中实现的简单结构。该控制器的缺点是响应时间长,稳定性裕度低以及对不必要数量的频率进行滤波。已经研究了使用许多陷波滤波器的替代控制策略。陷波滤波器可以调谐需要抑制的吨频率。该控制器可大大缩短系统响应时间并提高稳定性余量