首页> 外文期刊>IEEE Transactions on Power Systems >Analysis on the control principle of the active DC filter in the Lindome converter station of the Konti-Skan HVDC link
【24h】

Analysis on the control principle of the active DC filter in the Lindome converter station of the Konti-Skan HVDC link

机译:Konti-Skan高压直流输电线路Lindome换流站中有源直流滤波器的控制原理分析

获取原文
获取原文并翻译 | 示例
       

摘要

The control principle of a hybrid passive-active DC filter installed in the Lindome HVDC converter station is analyzed in this paper. The controller of the active filter includes two basic functions: an integrator and a compensator. The main advantage of the Lindome controller is its simple structure for implementation in a digital signal processor (DSP). The drawbacks of this controller are its long response time, low stability margin and the filtering of an unnecessary number of frequencies. An alternative control strategy using a number of notch filters has been investigated. The notch filters can be tuned to those frequencies that need to be damped. This controller gives a much shorter system response time and improved stability margin.
机译:本文分析了安装在Lindome HVDC换流站的混合型无源-有源DC滤波器的控制原理。有源滤波器的控制器包括两个基本功能:积分器和补偿器。 Lindome控制器的主要优点是其简单的结构,可在数字信号处理器(DSP)中实现。该控制器的缺点是响应时间长,稳定性裕度低以及对不必要数量的频率进行滤波。已经研究了使用许多陷波滤波器的替代控制策略。陷波滤波器可以调谐到需要衰减的频率。该控制器可大大缩短系统响应时间并提高稳定性裕度。