首页> 外文期刊>IEEE Transactions on Power Delivery >Dielectric behavior of GIS switching disconnectors comparison of possible phase opposition tests
【24h】

Dielectric behavior of GIS switching disconnectors comparison of possible phase opposition tests

机译:GIS隔离开关的介电性能可能的相位相反测试的比较

获取原文
获取原文并翻译 | 示例
           

摘要

The dielectric behavior of a GIS (gas-insulated switchgear) switching disconnector is investigated by means of full-phase opposition tests to obtain data on the discharge-to-ground phenomenon. This phenomenon, which is a function of the voltage across the disconnector switch contacts before restrike and of the amplitude of the overvoltage after restrike, displays a very large scatter. In addition, the time-to-crest of the overvoltage has a great influence on the discharge to ground. A discharge-to-ground mechanism to explain all of these features is proposed. The guarantees of same disconnector switching given by two possible phase opposition tests having different overvoltage shapes and amplitude are compared.
机译:通过全相对立试验研究了GIS(气体绝缘开关设备)隔离开关的介电性能,以获得有关接地现象的数据。这种现象是重击前隔离开关触点两端的电压的函数,也是重击后过电压幅度的函数,这种现象表现出非常大的分散性。另外,过电压到达峰值的时间对接地放电有很大的影响。提出了一种解释所有这些特征的接地放电机制。比较了两种可能的具有不同过电压形状和幅度的相位相反测试给出的相同隔离开关的保证。