Certification tests in accordance with the requirements of the recent IEC 61259 standard for switching of bus-charging current by disconnecters of a (three-phase enclosed) 145 kV gas insulated switchgear (GIS) are described. These tests are primarily aimed at verifying that the discharge between the disconnector contacts does not introduce internal arc faults. Special emphasis is given to the high-frequency measuring system, used to verify a sufficiently severe waveshape of switching transients in the MHz range. Three-phase tests were performed, showing phenomena that were not demonstrated in practice before: first, it was shown that phase-to-phase voltage transients with a higher amplitude than the phase-to-ground values do actually occur. Second, the phase-to-phase capacitive coupling of the busbar system could raise the trapped charge, left after at the load side of the installation after disconnection, to values above 1 pu. In addition, measurements of induced voltages in the secondary system are reported.
机译:描述了根据最新IEC 61259标准的要求进行的认证测试,该标准通过145 kV气体绝缘开关设备(GIS)的隔离开关来切换总线充电电流。这些测试主要旨在验证隔离开关触点之间的放电不会引入内部电弧故障。高频测量系统特别受重视,用于验证MHz范围内开关瞬变的足够严重的波形。进行了三相测试,显示了以前没有在实践中证明过的现象:首先,表明实际发生了幅度高于相间值的相间电压瞬变。其次,母线系统的相间电容耦合可以将截留的电荷(断开后留在设备的负载侧)提高到大于1 pu的值。另外,还报告了二次系统中感应电压的测量。