Reducing dead time for single-phase auto-reclosing on a series-capacitor compensated transmission line

机译:减少串联电容补偿传输线上单相自动重合的停滞时间

获取原文
获取原文并翻译 | 示例

摘要

This paper presents a single-phase auto-reclosing study of a 500 kV Vietnamese transmission line. The success of the single-phase auto-reclosing depends on the extinction of the secondary arc. Therefore, the influences of several factors such as shunt and neutral reactors, faulted phase and location, capacitive and inductive coupling and series capacitor discharge on the extinction of secondary arc are investigated. This paper presents the influence of single-phase auto-reclosing on the transient stability of the Vietnam system. A new method in order to reduce the dead time for single-phase auto-reclosing is proposed.
机译:本文提出了一条500 kV越南输电线路的单相自动重合闸研究。单相自动重合闸的成功取决于次级电弧的熄灭。因此,研究了并联电抗器和中性电抗器,故障相和位置,电容和电感耦合以及串联电容器放电等因素对次级电弧熄灭的影响。本文介绍了单相自动重合闸对越南系统暂态稳定性的影响。提出了一种减少单相自动重合的停滞时间的新方法。