首页> 外文期刊>IEEE Transactions on Power Delivery >Improvement of the Voltage Difference Method to Detect Arcing Faults Within Unfused Grounded-Wye 22.9-kV Shunt Capacitor Bank
【24h】

Improvement of the Voltage Difference Method to Detect Arcing Faults Within Unfused Grounded-Wye 22.9-kV Shunt Capacitor Bank

机译:检测未熔接地22.9 kV并联式并联电容器组中的电弧故障的电压差方法的改进

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an effective algorithm to protect unfused 22.9-kV shunt capacitor banks in grounded-wye connection by improving an existing voltage difference method-based algorithm. It has often been reported that it is difficult to detect ground faults with arc near the input points within the bank using existing algorithms that use only the magnitude of the differential voltage. In this paper, it is shown that ground faults with arc near the input point can be detected by fast Fourier transform (FFT) analysis of the differential voltage and that the proposed algorithm is not impacted by harmonics generated by nonlinear loads which have quantitative influence on the capacitor banks. Consequently, the proposed method using harmonics analysis can be applied as an extended version of the existing detection method. The proposed method is applied to a simplified 22.9-kV real-life Korea Electric Power Corporation system and it is verified that the proposed algorithm can clearly detect faults that are not easily detected by the existing method
机译:本文提出了一种有效的算法,通过改进现有的基于电压差方法的算法,可以保护未接地的22.9 kV并联电容器组。经常有报道说,使用仅使用差分电压幅度的现有算法,很难检测出在组内输入点附近有电弧的接地故障。本文表明,可以通过对差分电压进行快速傅立叶变换(FFT)分析来检测输入点附近具有电弧的接地故障,并且所提出的算法不受非线性负载产生的谐波的影响,该谐波对负载有定量影响。电容器组。因此,所提出的使用谐波分析的方法可以用作现有检测方法的扩展版本。将该方法应用于简化的22.9 kV现实生活的韩国电力公司系统,并验证了该算法可以清楚地检测到现有方法不易发现的故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号