首页> 外文期刊>Power Delivery, IEEE Transactions on >The Influence of Complex Permeability on the Broadband Frequency Response of a Power Transformer
【24h】

The Influence of Complex Permeability on the Broadband Frequency Response of a Power Transformer

机译:复磁导率对电力变压器宽带频率响应的影响

获取原文
获取原文并翻译 | 示例

摘要

This paper considers the effect of the complex permeability of a power transformer core on the frequency response analysis (FRA) test spectrum. Current work in FRA generally neglects the core beyond a few hundred kHz. This research demonstrates that the effective complex permeability is significant at 1 MHz and greater than unity at frequencies exceeding 15 MHz. The paper also shows that for broadband small signal testing, such as FRA, the low field conditions induced by the injected signal result in a relative permeability that approaches the initial permeability of the core. This ensures that the relative permeability remains approximately constant over a large range of frequencies and will have a degree of independence with respect to the amplitude of the injection voltage.
机译:本文考虑了电源变压器铁心的复数磁导率对频率响应分析(FRA)测试频谱的影响。 FRA中目前的工作通常会忽略数百kHz以上的内核。这项研究表明,有效复磁导率在1 MHz时很显着,而在超过15 MHz的频率时大于1。该论文还表明,对于宽带小信号测试(例如FRA),注入信号引起的低磁场条件会导致相对磁导率接近磁芯的初始磁导率。这确保了相对磁导率在较大的频率范围内保持近似恒定,并且相对于注入电压的幅度具有一定程度的独立性。