Arcing line connectors caused interference

机译:电弧线连接器引起干扰

获取原文
获取原文并翻译 | 示例
       

摘要

A baffling case of radio interference caused much distress to the citizens of Albert Lea, Minn., some time ago. The interference manifested itself as a continuous sound, obviously caused by a maintained arc. It was finally located by means of a portable set inside of a sleeve clamp connecting an aluminum to a copper conductor on a transmission line on the outskirts of the city. The hole in the connector for the reception of the aluminum conductor was fined with aluminum and the hole for the copper conductor was lined with copper. The man who installed the connector reversed it so that the contacts were between unlike, instead of like, metals. Corrosion occurred in the course of time, until finally an arcing contact was established. When the connector was replaced the interference ceased, thus terminating a prolific source of radio complaints. — Electrical World.
机译:不久前,令人困惑的无线电干扰案给明尼苏达州的阿尔伯特·利阿市民造成了极大的困扰。干扰本身表现为连续的声音,显然是由保持的电弧引起的。最终通过便携式夹具将其定位在套筒夹内,该套筒夹将铝和铜导体连接到城市郊区的传输线上。连接器中用于容纳铝导体的孔用铝细化,并且用于铜导体的孔衬有铜。安装该连接器的人将其颠倒过来,以使触点位于不同的金属之间,而不是类似的金属之间。随着时间的流逝发生腐蚀,直到最终建立起电弧接触。更换连接器后,干扰就停止了,从而终止了大量的无线电投诉。 —电气世界。