Distance relaying of 11 kV circuits to increase the installed capacity of distributed generation

机译:11 kV电路的距离继电器,以增加分布式发电的装机容量

获取原文
获取原文并翻译 | 示例

摘要

The connection of generation to distribution networks may cause problems with existing protection schemes, while development of new protection schemes can facilitate an increase in generation capacity. The design and evaluation of a distribution network protection scheme based on distance relays is described. The scheme provides primary and back-up protection of 11 kV circuits. In the UK, voltage transformers and communication schemes are seldom installed on 11 kV circuits. Hence the distance relay restraint signal (voltage) is measured at the secondary winding of a distribution transformer (1 1/0.433 kV) to reduce costs. The development of the distance relay algorithm is discussed and a selection of simulation test results provided to illustrate the relay performance under fault conditions.
机译:发电与配电网络的连接可能会导致现有保护方案出现问题,而开发新的保护方案可以促进发电容量的增加。描述了基于距离继电器的配电网保护方案的设计和评估。该方案可为11 kV电路提供初级和备用保护。在英国,很少在11 kV电路上安装电压互感器和通信方案。因此,在配电变压器的次级绕组(1/1 / 0.433 kV)处测量距离继电器抑制信号(电压)以降低成本。讨论了距离继电器算法的发展,并提供了一些仿真测试结果,以说明故障条件下的继电器性能。