Practical Experience with Full-scale Performance Verification of Dynamic Vibration Absorbers installed in Tall Buildings

机译:具有在高层建筑中安装的动态减振器的全规模性能验证的实践经验

获取原文
获取原文并翻译 | 示例
       

摘要

Dynamic vibration absorbers (DVAs) in the form of tuned sloshing dampers (TSDs) and tuned mass dampers (TMDs) are commonly used to reduce the wind-induced motion of high-rise buildings. Full-scale performance of structure-DVA systems must be evaluated during the DVA commissioning process using structural monitoring data. While the random decrement technique (RDT) is sometimes employed to evaluate the DVA performance, it is shown to have no theoretical justification for application to structure-DVA systems, and to produce erroneous results. Subsequently, several practical methods with a sound theoretical basis are presented and illustrated using simulated and real-world data. By monitoring the responses of the structure and DVA simultaneously, it is possible to directly measure the effective damping of the system or perform system identification from which the DVA performance can be evaluated.
机译:调谐晃动阻尼器(TSD)和调谐质量阻尼器(TMDS)形式的动态减振器(DVA)通常用于减少高层建筑的风力诱导的运动。 必须在使用结构监测数据的DVA调试过程中进行结构-DVA系统的全尺寸性能。 虽然有时采用随机递减技术(RDT)来评估DVA性能,但它显示在结构-DVA系统中没有理论上的理论,并产生错误的结果。 随后,使用模拟和现实世界数据来提出和说明具有声音理论基础的几种实用方法。 通过同时监视结构和DVA的响应,可以直接测量系统的有效阻尼,或者执行可以评估DVA性能的系统识别。