In this paper, a multichannel instrumentation system for the location of partial discharges (PDs) in power transformers is presented. It is based on the detection of the acoustic emissions from PDs in oil with several piezoelectric (PZT) and fiber optic sensors. An acoustic detection and location approach is proposed based on a time reference given by one fiber optic sensor installed inside the tank and the times of arrival to several PZT sensors installed outside the tank (two in front of each phase windings of a three phase transformer for a typical application). The signal processing includes digital denoising techniques and time-difference lookup table-based 3-D location algorithms; these algorithms have been implemented with virtual instrumentation. The system is tested in an acoustic experimental setup and the location accuracy is evaluated. Finally, the error propagation from the times of arrival and the influence of the number of sensors and their sites in the 3-D location algorithm were analyzed.
机译:本文提出了一种用于电力变压器局部放电(PDs)定位的多通道仪表系统。它基于使用多个压电(PZT)和光纤传感器检测石油中PD的声发射。根据安装在储罐内部的一个光纤传感器给出的时间基准,以及到达安装在储罐外部的多个PZT传感器的到达时间(三相变压器每个相绕组的前面两个)的时间,提出了一种声音检测和定位方法。典型应用)。信号处理包括数字降噪技术和基于时差查找表的3-D定位算法;这些算法已通过虚拟仪器实现。该系统在声学实验装置中进行了测试,并评估了定位精度。最后,分析了在3D定位算法中到达时间的误差传播以及传感器数量及其位置的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号