This paper presents the design consideration and performance analysis of an on-line, low-cost, high performance, and single-phase uninterruptible power supply (UPS) system based on a boost integrated flyback rectifier/energy storage dc/dc (BIFRED) converter. The system consists of an isolated ac/dc BIFRED converter, a bidirectional dc/dc converter, and a dc/ac inverter. It provides input power factor correction, electric isolation of the input from the output, low battery voltage, and control simplicity. Unlike conventional UPS topologies, the electrical isolation is provided using a high frequency transformer that results in a smaller size and lower cost. Detailed circuit operation, analysis, as well as simulation and experiment results are presented. A novel digital control technique is also presented for UPS inverter control. This controller follows the reference current and voltage of the inverter with a delay of two and four sampling periods, respectively.
机译:本文介绍了基于升压集成反激式整流器/储能DC / DC(BIFRED)转换器的在线,低成本,高性能,单相不间断电源(UPS)系统的设计考虑和性能分析。该系统由一个隔离的AC / DC BIFRED转换器,一个双向DC / DC转换器和一个DC / AC逆变器组成。它提供输入功率因数校正,输入与输出的电隔离,低电池电压以及控制简便性。与传统的UPS拓扑不同,电气隔离是使用高频变压器提供的,从而减小了尺寸并降低了成本。给出了详细的电路操作,分析以及仿真和实验结果。还提出了一种新颖的数字控制技术,用于UPS逆变器控制。该控制器分别以两个和四个采样周期的延迟跟踪逆变器的参考电流和参考电压。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号