Worker performance and ventilation in a call center: analyses of work performance data for registered nurses

机译:呼叫中心的员工绩效和通风:注册护士的工作绩效数据分析

获取原文
获取原文并翻译 | 示例
           

摘要

We investigated the relationship between ventilation rates and individual work performance in a call center, and controlled for other factors of the indoor environment. We randomized the position of the outdoor air control dampers, and measured ventilation rate, differential (indoor minus outdoor) carbon dioxide (ΔCO_2) concentration, supply air velocity, temperature, humidity, occupant density, degree of under-staffing, shift length, time of day, and time required to complete two different work performance tasks (talking with clients and post-talk wrap-up to process information). ΔCO_2 concentrations ranged from 13 to 611 p.p.m. We used multivariable regression to model the association between the predictors and the responses. We found that agents performed talk tasks fastest when the ventilation rate was highest, but that the relationship between talk performance and ventilation was not strong or monotonic. We did not find a statistically significant association between wrap-up performance and ventilation rate. Agents were slower at the wrap-up task when the temperature was high ( > 25.4℃). Agents were slower at wrap-up during long shifts and when the call center was under-staffed.
机译:我们调查了呼叫中心的通风率与个人工作绩效之间的关系,并控制了室内环境的其他因素。我们将室外空气调节风门的位置随机化,并测量通风率,差(室内减去室外)二氧化碳(ΔCO_2)浓度,送风速度,温度,湿度,乘员密度,人员不足程度,班次长度,时间时间和完成两个不同的工作绩效任务所需的时间(与客户交谈和交谈后总结以处理信息)。 ΔCO_2浓度范围为13至611p.p.m。我们使用多元回归对预测变量和响应之间的关联进行建模。我们发现,当通气率最高时,座席执行谈话任务的速度最快,但是谈话性能和通气之间的关系并不牢固或单调。我们没有发现包卷性能和通气率之间有统计学意义的关联。当温度较高(> 25.4℃)时,包裹剂的包裹速度较慢。长时间轮班时以及呼叫中心人员不足时,座席的处理速度较慢。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号