首页> 外文期刊>IEEE Transactions on Power Electronics >Performance of a self-commutated BTB HVDC link system under a single-line-to-ground fault condition
【24h】

Performance of a self-commutated BTB HVDC link system under a single-line-to-ground fault condition

机译:自换向BTB HVDC链路系统在单线接地故障条件下的性能

获取原文
获取原文并翻译 | 示例

摘要

This paper deals with a self-commutated back-to-back (BTB) high-voltage direct-current (HVDC) link system for the purpose of power flow control and/or frequency change in transmission systems. Each BTB unit consists of two sets of 16 three-phase voltage-source converters, and their AC terminals are connected in series each other via 16 three-phase transformers. Hence, the BTB unit uses totally 192 switching devices capable of achieving gate commutation. This results in a great reduction of voltage and current harmonics without performing PWM control. Simulation results verify the validity of the proposed system configuration and control scheme not only under a normal operating condition but also under a single-line-to-ground fault condition.
机译:本文研究了一种自换向背对背(BTB)高压直流(HVDC)链接系统,目的是控制输电系统中的功率流和/或改变频率。每个BTB单元由两组16个三相电压源转换器组成,它们的AC端子通过16个三相变压器彼此串联。因此,BTB单元使用总共192个能够实现门换向的开关装置。这样可以在不执行PWM控制的情况下大大降低电压和电流谐波。仿真结果验证了所提出的系统配置和控制方案的有效性,不仅在正常操作条件下,而且在单线接地故障条件下也是如此。