首页> 外文期刊>IEEE Transactions on Power Electronics >Optimized Control Strategy for a Medium-Voltage DVR—Theoretical Investigations and Experimental Results
【24h】

Optimized Control Strategy for a Medium-Voltage DVR—Theoretical Investigations and Experimental Results

机译:中压DVR的最佳控制策略—理论研究和实验结果

获取原文
获取原文并翻译 | 示例

摘要

Most power quality problems in distribution systems are related to voltage sags. Therefore, different solutions have been examined to compensate these sags to avoid production losses at sensitive loads. Dynamic Voltage Restorers (DVRs) have been proposed to provide higher power quality. Currently, a system wide integration of DVRs is hampered because of their high cost, in particular, due to the expensive DC-link energy storage devices. The cost of these DC-link capacitors remains high because the DVR requires a minimum DC-link voltage to be able to operate and to compensate a sag. As a result, only a small fraction of the energy stored in the DC-link capacitor is used, which makes it impractical for DVRs to compensate relatively long voltage sags. Present control strategies are only able to minimize the distortions at the load or to allow a better utilization of the storage system by minimizing the needed voltage amplitude. To avoid this drawback, an optimized control strategy is presented in this paper, which is able to reduce the needed injection voltage of the DVR and concurrently to mitigate the transient distortions at the load side. In the following paper, a brief introduction of the basic DVR principle will be given. Next, three standard control strategies will be compared and an optimized control strategy is developed in this paper. Finally, experimental results using a medium-voltage 10-kV DVR setup will be shown to verify and prove the functionality of the presented control strategy in both symmetrical and asymmetrical voltage sag conditions.
机译:配电系统中的大多数电能质量问题都与电压骤降有关。因此,已经研究了不同的解决方案来补偿这些下垂,以避免敏感负载下的生产损失。动态电压恢复器(DVR)已被提议提供更高的电能质量。当前,由于DVR的高成本,特别是由于昂贵的DC链路能量存储设备,DVR的系统范围的集成受到阻碍。这些直流母线电容器的成本仍然很高,因为DVR需要最低的直流母线电压才能工作并补偿下垂。结果,仅使用了存储在直流母线电容器中的能量的一小部分,这使得DVR无法补偿相对较长的电压骤降。当前的控制策略仅能够通过最小化所需的电压幅度来最小化负载处的畸变或允许更好地利用存储系统。为避免这一缺点,本文提出了一种优化的控制策略,该策略能够降低DVR所需的注入电压,并同时减轻负载侧的瞬态失真。在下面的文章中,将简要介绍DVR的基本原理。接下来,将对三种标准控制策略进行比较,并提出一种优化的控制策略。最后,将显示使用中压10 kV DVR设置的实验结果,以验证和证明所提出的控制策略在对称和不对称电压骤降条件下的功能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号