Fault isolation in distributed generation connected distribution networks

机译:分布式发电连接配电网中的故障隔离

获取原文
获取原文并翻译 | 示例

摘要

Protection of a distribution network in the presence of distributed generators (DGs) using overcurrent relays is a challenging task because of the changes in fault current levels and reverse power flow. Specifically, in the presence of current limited converter interfaced DGs, overcurrent relays may fail to isolate the faulted section either in grid connected or islanded mode of operation. In this study, a new inverse-type relay is presented to protect a distribution network, which may have several DG connections. The new relay characteristic is designed based on the measured admittance of the protected line. The relay is capable of detecting faults under changing fault current levels. The relay performance is evaluated using PSCAD simulation and laboratory experiments.
机译:在存在使用过电流继电器的分布式发电机(DG)的情况下保护配电网络是一项艰巨的任务,因为故障电流水平和反向功率流会发生变化。特别是,在存在限流转换器接口的DG的情况下,过电流继电器可能无法以电网连接或孤岛运行模式隔离故障部分。在这项研究中,提出了一种新的反型继电器来保护可能具有多个DG连接的配电网络。新的继电器特性是根据测得的保护线导纳设计的。继电器能够在不断变化的故障电流水平下检测故障。使用PSCAD仿真和实验室实验评估继电器的性能。