This study represents experimental techniques for testing the high-voltage polluted insulators under conditions simulating the natural environment. International Electrotechnical Commission (IEC) fog method is used for testing the insulators of type π-φ-E4.5, but it does not simulate the desert pollution environments. For that reason, other two suggested techniques are added to explain the performance of the polluted insulators under dew and under simultaneous fog and dew, respectively. The leakage current bursts are recorded in each test type. Also the effect of the wetting method of the insulators under testing on the flashover voltage is investigated. The results of the three types of tests are compared with each other, under different surface layer conductivities. It is concluded that the analysis of leakage current bursts can be used to monitor the severity of pollution on the electrical network.
机译:这项研究代表了在模拟自然环境的条件下测试高压污染绝缘子的实验技术。国际电工委员会(IEC)的雾化方法用于测试π-φ-E4.5型绝缘子,但它并未模拟沙漠污染环境。因此,添加了另外两种建议的技术来分别解释受污染的绝缘子在露水和同时起雾和露水下的性能。每种测试类型都会记录泄漏电流突发。还研究了被测绝缘子的润湿方法对闪络电压的影响。在不同的表层电导率下,将三种测试的结果相互比较。结论是,泄漏电流突发的分析可用于监视电网污染的严重性。