This paper presents an experimental study to investigate the performance of intumescent coatings exposed to large space fires, focusing on the feasibility of a three stage constant effective thermal conductivity model. A total of 54 steel plate specimens protected with intumescent coatings of different thicknesses were tested under ISO 834 fire and three large space fire temperature-time curves. It was found that the performance of intumescent coatings could be divided into three different stages: melting, expanding and full expansion, corresponding to the steel temperature ranges of 100 degrees C-300 degrees C, 300 degrees C-400 degrees C and above 400 degrees C respectively. The feasibility of representing the temperature dependent thermal conductivity of intumescent coatings in large space fires by three stage constant effective thermal conductivities was validated with the tests. The relations between constant effective thermal conductivities of three stages and that under ISO 834 fire were investigated. The applicability of the proposed model for large space fires has been checked by comparison between the calculated steel temperatures using the proposed model and the test results. The proposed model allows the fire test results under ISO 834 fire to be adapted to large space fires, and simplifies the temperatures calculation procedure of intumescent coating protected steel in large space fires.
机译:本文提出了一项实验研究,以研究暴露于大空间火灾的膨胀型涂料的性能,重点是三阶段恒定有效导热系数模型的可行性。在ISO 834防火标准和三条大空间防火温度-时间曲线下,总共测试了54个用不同厚度的膨胀涂层保护的钢板样品。发现膨胀型涂层的性能可分为三个不同的阶段:熔化,膨胀和完全膨胀,分别对应于100摄氏度至300摄氏度,300摄氏度至400摄氏度以及400摄氏度以上的温度范围C分别。通过试验验证了用三阶段恒定有效热导率表示大空间火灾中膨胀型涂料的温度依赖性热导率的可行性。研究了三个阶段的恒定有效热导率与ISO 834火灾下的热导率之间的关系。通过比较使用提议模型计算的钢温度和测试结果,检查了提议模型在大型空间火灾中的适用性。所提出的模型允许将ISO 834火灾下的火灾测试结果调整为适合大空间火灾,并简化了大空间火灾中膨胀型涂层保护钢的温度计算程序。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号