首页> 外文期刊>IEEE Transactions on Electrical Insulation >Free particle-initiated 60 Hz breakdown at a spacer surface in a gas-insulated bus
【24h】

Free particle-initiated 60 Hz breakdown at a spacer surface in a gas-insulated bus

机译:气体绝缘母线在隔离物表面发生自由粒子引发的60 Hz击穿

获取原文
获取原文并翻译 | 示例

摘要

The influence of freely moving wire particles on 60-Hz AC surface flashover of epoxy and acrylic disk spacers in a 76/250 mm coaxial system was examined in sulfur hexafluoride gas at pressures of 300 and 500 kPa. The experimental results show that 0.45-mm-diameter aluminium wire particles, 6.4 mm long, will lift and reach a nearby spacer at voltages comparable to system operating voltage. The combination of metallic particles and spacer does not reduce the breakdown voltage below that for free particles without a spacer unless a particle is lodged on the spacer very close (>2 mm) to the center conduction. The probability of this occurring is much greater for horizontal disk or conical spacers than for vertically mounted disk spacers. The results are of interest in connection with the operation of GITL/GIS (gas-insulated transmission line/gas-insulated substation and switchgear) systems.
机译:在六氟化硫气体中分别在300和500 kPa的压力下,检查了自由移动的导线颗粒对76/250 mm同轴系统中的环氧树脂和丙烯酸盘形垫片的60 Hz AC表面闪络的影响。实验结果表明,直径为0.45毫米,长6.4毫米的铝线颗粒将在与系统工作电压相当的电压下升起并到达附近的垫片。金属粒子和隔离物的组合不会将击穿电压降低到低于没有隔离物的自由粒子的击穿电压,除非粒子沉积在距离中心传导非常近(> 2 mm)的隔离物上。对于水平盘形或圆锥形垫片,发生这种情况的可能性要比垂直安装的盘形垫片大得多。该结果与GITL / GIS(气体绝缘传输线/气体绝缘变电站和开关设备)系统的运行有关。