To investigate the effect of air-conditioning parameters (including temperature, relative humidity and air velocity) and deposition dust on microbial growth in supply air duct, a complete test facility according to ASHRAE Standard 62.1-2007 was constructed. A series of experiments for testing microbial concentration (including bacteria and fungus) were conducted under different working conditions (such as different temperatures and relative humidity). The air velocity was constantly kept at 2.0 m/s. Orthogonal design was employed for the analysis of test data. The results indicated that air velocity attenuation down the direction of the supply air affected dust distribution at the bottom of duct, to some extent, and the number of microorganisms was positively correlated with the quantity of dust. In the range of temperature 22-32 ℃ and relative humidity (RH) 40-90%, microbial growth significantly accelerated with higher temperature and RH increasing. The organic compounds composing the dust also had great impact on microbial growth. The basic researches are contributed to control the growth of microorganism and improve the indoor microenvironment in the air-conditioning room.
机译:为了研究空调参数(包括温度,相对湿度和空气速度)和沉积粉尘对送风管道中微生物生长的影响,根据ASHRAE标准62.1-2007建立了完整的测试设施。在不同的工作条件(例如不同的温度和相对湿度)下进行了一系列测试微生物浓度(包括细菌和真菌)的实验。空气速度始终保持在2.0 m / s。正交设计用于测试数据的分析。结果表明,送风方向的风速衰减在一定程度上影响了风管底部的粉尘分布,微生物数量与粉尘量呈正相关。在温度22-32℃和相对湿度(RH)40-90%的范围内,微生物的生长随着温度的升高和相对湿度的增加而明显加速。构成粉尘的有机化合物也对微生物的生长有很大影响。基础研究有助于控制微生物的生长,改善空调室内的室内微环境。

著录项

  • 来源
    《Energy and Buildings》 |2010年第4期|p.449-454|共6页
  • 作者单位

    School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, Xi'an, Shannxi 710055, PR China;

    School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, Xi'an, Shannxi 710055, PR China;

    School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, Xi'an, Shannxi 710055, PR China;

    School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, Xi'an, Shannxi 710055, PR China;

    China Academy of Building Research, Beijing 100013, PR China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    air velocity; microorganisms; deposition dust; temperature; supply air duct; relative humidity;