To improve system efficiency under part-load conditions, the supply air temperature set point for a single-duct constant air volume air handling unit (AHU) system is often reset based on either return air temperature or outside air temperature. Both reset strategies make engineering sense as long as the reset schedules are reasonable. Quite often the decision to use one over the other is made with the assumption that they will both achieve some energy savings. However, the impact of these two strategies on AHU energy consumption could be very different. An in-depth analysis and comparison of these two commonly used supply air temperature reset strategies for a single-duct constant air volume system is presented in this paper. It is shown that the reset strategy based on outside air temperature is inherently better than that based on return air temperature, with lower energy consumption and improved building comfort level.
机译:为了提高部分负载条件下的系统效率,通常会根据回风温度或外界空气温度来重置单通道恒定风量空气处理单元(AHU)系统的送风温度设定点。只要重置时间表合理,这两种重置策略都具有工程意义。通常,一个使用另一个选项的决定是基于它们都将实现一定的节能效果。但是,这两种策略对AHU能耗的影响可能会非常不同。本文对单通道恒定风量系统这两种常用的送风温度复位策略进行了深入的分析和比较。结果表明,基于外部空气温度的复位策略本质上要优于基于返回空气温度的复位策略,具有更低的能耗和更高的建筑舒适度。