首页> 美国政府科技报告 >PI Control of a Single-Duct VAV (Variable Air Volume) HVAC (Heating, Ventilating, and Air Conditioning) System
【24h】

PI Control of a Single-Duct VAV (Variable Air Volume) HVAC (Heating, Ventilating, and Air Conditioning) System

机译:单风道VaV(可变风量)HVaC(加热,通风和空调)系统的pI控制

获取原文

摘要

This manuscript documents an investigation of the feedback control of a variable air volume heating and air-conditioning system for a moderately sized multiroom building. The primary objective was to determine if commonly applied single-loop control system desing principles are adequate for designing air-conditioning control systems. The research established that the sensitivity of the single-input single-output conventional design to the presence of the multi-input multi-output interconnection was insignificant. Also, the Ziegler-Nichols control parameter tuning technique produced highly oscillatory control systems when applied to an air-conditioning system. Modified tuning formulas are presented.