Field and Laboratory Measurements on Dust Associated with Microbial Contamination in Centralized Air-Conditioning Systems

机译:中央空调系统中与微生物污染相关的粉尘的现场和实验室测量

获取原文

摘要

The objective of this study was field test and laboratory measurements to investigate the dust associated with microbial contamination (including bacteria and fungi) characteristics in an air conditioning system. The case study, the centralized air conditioning system at Shaanxi History Museum, has been carded out. It was found that dust weight were at the range of 2.76~22.30 g/m2, and microbiological concentration ranged from 1.14x104cfu/g to 10.86x 104cfu/g. The dominating genera of fungi in dust were Cladosporium spp.(winter=34.3% and summer=41.8%) and Penicillium spp.( winter=23.6% and summer=30.1%).The results showed that there was microorganism growth inside the ventilation ducts, especially fungi were found in the ventilation duct. It suggests that the HVAC-systems of the building should be improved the filter efficiency and installed the control and disinfection device to mitigate the microbiological pollution.
机译:这项研究的目的是现场测试和实验室测量,以研究空调系统中与微生物污染(包括细菌和真菌)特征有关的粉尘。该案例研究,即陕西历史博物馆的中央空调系统,已经被淘汰。结果表明:粉尘重量为2.76〜22.30 g / m2,微生物浓度为1.14×104cfu / g〜10.86×104cfu / g。尘土中真菌的主要属为克拉德孢子菌(冬季= 34.3%,夏季= 41.8%)和青霉菌(冬天= 23.6%,夏季= 30.1%),结果表明通风管道内有微生物生长。 ,尤其是在通风管道中发现了真菌。这建议应提高建筑物的暖通空调系统的过滤效率,并安装控制和消毒装置以减轻微生物污染。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号