首页> 外文期刊>IEEE Transactions on Electromagnetic Compatibility >Transient response of a distribution circuit recloser and control unit to a high-altitude electromagnetic pulse (HEMP) and lightning
【24h】

Transient response of a distribution circuit recloser and control unit to a high-altitude electromagnetic pulse (HEMP) and lightning

机译:配电电路重合器和控制单元对高海拔电磁脉冲(HEMP)和雷电的瞬态响应

获取原文
获取原文并翻译 | 示例

摘要

An analysis of the response of a power system distribution line recloser unit to a high-altitude electromagnetic pulse (HEMP) and a lightning direct-strike excitation is presented. From details of the configuration of the system, physical and mathematical models are developed, and a study of possible HEMP responses is conducted. Two voltage and two current responses at selected points within the system are studied for both the HEMP and lightning stresses. The possibility of simulating the HEMP responses is also discussed, with predicted and measured responses being provided for the advanced research EMP simulator (ARES). Based on a comparison of measured and predicted currents on one of the conductors, the model is shown to agree reasonably well with the measurement. With such a model, it is possible to perform parametric studies of the HEMP response of the system.
机译:提出了配电系统重合闸单元对高空电磁脉冲(HEMP)和雷电直接打击激励的响应的分析。根据系统配置的详细信息,开发了物理和数学模型,并对可能的HEMP响应进行了研究。针对HEMP和雷击应力,研究了系统中选定点的两个电压和两个电流响应。还讨论了模拟HEMP响应的可能性,并为高级研究EMP模拟器(ARES)提供了预测和测量的响应。基于对其中一根导体上的测量电流和预测电流的比较,表明该模型与测量值相当吻合。使用这种模型,可以对系统的HEMP响应进行参数研究。