首页> 外文期刊>Electrical Engineers, Proceedings of the Institution of >Transient voltages generated by inductive switching in control circuits
【24h】

Transient voltages generated by inductive switching in control circuits

机译:控制电路中感应开关产生的瞬态电压

获取原文
           

摘要

In certain control applications a common d.c. supply is used for both electronic and electromechanical equipment. In this situation semiconductor devices may be subjected to transient voltages generated by the operation of mechanical switches in inductive circuits. This paper describes the factors involved in the generation of such transients and methods for predicting their time duration are proposed. The circuit interruption process is described in terms of either stable or unstable arc switching and the limiting factors for these two conditions are discussed. It is shown that when unstable arc switching occurs short-duration voltage spikes appear across the common power supply and, by implication, across all parallel-connected equipment. Reasonable correlation is shown to exist between predicted and measured transient-voltage time durations and the analytical models proposed could be used as a theoretical basis for transient-voltage specifications.
机译:在某些控制应用中,常见的直流电电源用于电子和机电设备。在这种情况下,半导体器件可能会受到感应电路中机械开关操作产生的瞬态电压的影响。本文介绍了产生此类瞬变的因素,并提出了预测其持续时间的方法。根据稳定或不稳定电弧切换来描述电路中断过程,并讨论了这两种情况的限制因素。结果表明,当发生不稳定的电弧切换时,在公共电源两端以及所有并联设备上都会出现短时电压尖峰。结果表明,预测的和测量的瞬态电压持续时间之间存在合理的相关性,并且所提出的分析模型可以用作瞬态电压指标的理论基础。

著录项