Partial Discharge Pulse Sequence Patterns and Cavity Development Times in Transformer Oils under ac Conditions

机译:交流条件下变压器油中的局部放电脉冲序列模式和腔发展时间

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Discrete partial discharge (PD) pulse occurrence times within the PD pulse bursts in transformer oils were found to extend from approximately 0.42 to 2.9 μS, with the discrete pulse separation times evincing a weak dependence on the inverse of the oil viscosity. Many PD pulse burst patterns exhibited substantial deviation from the classical behavior, which is normally characterized by successive discrete pulses of ascending amplitude with well defined increases in the pulse separation times. The average elapsed time from the incipient formation for the cavity to the onset of the first partial discharge event extended downwards from 0.62 to 0.42 μs with increasing oil viscosity.
机译:发现变压器油中PD脉冲猝发内的离散局部放电(PD)脉冲发生时间从大约0.42扩展到2.9μS,离散脉冲分离时间表明对油粘度倒数的依赖性很弱。许多PD脉冲突发模式表现出与经典行为的显着偏差,通常以连续上升的离散离散脉冲为特征,并明确定义了脉冲分离时间的增加。随着油粘度的增加,从腔体开始形成到第一次局部放电事件开始的平均经过时间从0.62μs向下延伸至0.42μs。