首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Condition assessment of XLPE insulated cables based on polarization/depolarization current method
【24h】

Condition assessment of XLPE insulated cables based on polarization/depolarization current method

机译:基于极化/去极化电流法的交联聚乙烯绝缘电缆状态评估

获取原文
获取原文并翻译 | 示例

摘要

The water tree is one of the key factors leading to the insulation property deterioration in cross-linked polyethylene (XLPE) cables. An accelerated ageing experiment has been performed to produce water trees with the purpose of ageing the full-size XLPE cable under the high-frequency electric field. Based on Polarization and Depolarization Current (PDC) method, the diagnostic tests are employed to evaluate the ageing extent of the cable subjected to water tree at different ageing time. Results show that the average length of water trees is proportional to the ageing time, and thus the experiment is effective to accelerate the growth of water trees. Furthermore, such various diagnostic indicators as the I∗t∼lnt curves, the loss factor at different frequency, have their rules to assess the ageing condition of the cable with the duration of ageing time. Therefore, information obtained from PDC current can be used for determining the ageing extent of the cables.
机译:水树是导致交联聚乙烯(XLPE)电缆绝缘性能下降的关键因素之一。为了在高频电场下老化全尺寸XLPE电缆,已经进行了加速老化实验以生产水树。基于极化和去极化电流(PDC)方法,通过诊断测试来评估水树在不同老化时间下的老化程度。结果表明,水生树木的平均长度与衰老时间成正比,因此该实验有效地促进了水生树木的生长。此外,各种诊断指标,如I * t〜lnt曲线,不同频率下的损耗因子,都有其规则,可根据老化时间来评估电缆的老化条件。因此,从PDC电流获得的信息可用于确定电缆的老化程度。