首页> 外文期刊>ire Science and Technology >Interaction Between Hot Layer and Updraft from a Smoldering Fire Source - Part I An Experimental Approach -
【24h】

Interaction Between Hot Layer and Updraft from a Smoldering Fire Source - Part I An Experimental Approach -

机译:阴燃火源热层与上升气流之间的相互作用-第一部分实验方法-

获取原文
           

摘要

References(12) Cited-By(1) The heat generation values for the typical smoldering fire sources which have been proposed as the ISO Standard on Fire Detector Test were estimated experimentally based on oxygen consumption and weight loss rates. Heat generation values of smoldering wood and cotton wick showed 1/10 - 1/3 of those of flaming phase. The heat generation rate which was proposed as the Standard of ISO Fire Source was 1.5 kW and gave excess temperature of 2 - 2.5°C under the ceiling of the proposed ISO test room. It was found experimentally using the test room and proposed smoldering fire sources that the hot layer under the ceiling of which excess temperature of 2 - 3°C stopped the penetration of updraft smoke from the smoldering source through the thermal interface. It should be necessary that the exact definition on vertical thermal condition for the proposed ISO Test method to get repeatability, reliability, and sensitivity of the fire detector tests.
机译:参考文献(12)引用依据(1)根据氧气消耗量和失重率,通过实验估算了作为ISO火灾探测器测试标准提出的典型阴燃火源的发热量。阴燃的木芯和棉芯的生热值显示为燃烧相的1/10-1/3。提议作为ISO火源标准的发热量为1.5 kW,并在提议的ISO测试室的天花板下产生2-2.5°C的高温。通过实验在试验室中发现并提出了闷燃火源,其天花板下2-3°C的高温下的热层阻止了闷燃源的上升气流通过热界面渗透。对于拟议的ISO测试方法,有必要对垂直热条件进行准确定义,以获取火灾探测器测试的可重复性,可靠性和敏感性。