Low complexity, insensitivity on the system parameters, lesser number of electrical sensors, fast and accurate dynamic response, the ability of connection to weak AC system and high power quality are some of the major criterions for selection of control method of the voltage source converters (VSC). Considering these issues, in this paper, a new control method is presented for application in the VSC stations. This control method is based on recursive least squares with variable forgetting factor (VFF-RLS) which is a numerical estimator. Estimation of fundamental components of distorted AC grid voltage and their symmetric positive components are done by VFF-RLS estimators. Desired power injection by the proposed control method is done with corresponding to estimated signals. Simulation results in the MATLAB/SIMULINK platform and experimental results using TMS320F2812 digital signal processor validate the superiority of the proposed control method.
机译:低复杂度,对系统参数不敏感,更少的电传感器,快速准确的动态响应,与弱交流系统的连接能力以及高电能质量是选择电压源转换器控制方法的主要标准( VSC)。考虑到这些问题,本文提出了一种在VSC站中应用的新控制方法。此控制方法基于具有变量遗忘因子(VFF-RLS)的递归最小二乘,它是一种数值估计器。失真的交流电网电压的基本成分及其对称正成分的估计由VFF-RLS估计器完成。所提出的控制方法的期望功率注入是与估计的信号相对应的。在MATLAB / SIMULINK平台上的仿真结果以及使用TMS320F2812数字信号处理器的实验结果证明了该控制方法的优越性。